Register to unlock your exclusive B2B prices. Register now
MD01 image 1
Acti9 ID K - residual current circuit breaker - 4P - 40A - 30mA - type AC image 2
Acti9 ID K - residual current circuit breaker - 4P - 40A - 30mA - type AC image 3
Acti9 ID K - residual current circuit breaker - 4P - 40A - 30mA - type AC image 4

Acti9 ID K - residual current circuit breaker - 4P - 40A - 30mA - type AC

In stock price (excl. VAT):
35,81 €
This price is valid until 2024-05-30
Price per m: 35,81 €
EAN: 3606480473913
MPN: A9Z05440
Our warehouse: No Vendor stock: Yes
Per package: 1 Per box: 27 Per pallet: 216
Technical data
Item condition New
Brand Schneider Electric
Categories Leakage protection
Mounting method DIN rail
Voltage type AC
Built-in depth 44 mm
Rated current 40 A
Rated voltage 415 V
Rated insulation voltage Ui 440 V
Number of poles 4
Rated fault current 30 A
Leakage current type AC
Selective protection No
Short-circuit breaking capacity (Icw) 10 kA
Surge current capacity 0.25 kA
Pollution degree 2
Width in number of modular spacings 4
Short-time delayed tripping No
Explosion-proof No
Frequency 50/60 Hz
Degree of protection (IP) IP20
Connectable conductor cross section solid-core 1-35 mm²
Connectable conductor cross section multi-wired 1-25 mm²
With interlocking device No
Ambient temperature during operating -5-40 °C
Additional equipment possible Yes
Rated impulse withstand voltage Uimp 4 kV
Packing details
Packing level 1 3606480473913
Packing level 2 3606480473911
Packing level 3 3606480473913
Downloads
Description
This product is a Acti9 ID K biconnect residual current circuit breaker (RCCB). It is a 4P circuit breaker with 40A In rated current, a sensitivity of 30mA with a AC type protection class. This product protects against electrical shock by direct or indirect contact and fire hazards. There is a test button used to check the residual current device is operating correctly. The connection is made downstream by biconnect comb busbar or upstream/downstream by tunnel terminals. This product is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 500A. The (Inc/IΔc) conditional rated short circuit current is 4.5kA. The mechanical endurance is going up to 5000 cycles and electrical endurance going up to 2000 cycles. The Ue operational voltage is 380VAC to 415VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is white (RAL9003). The dimensions are (W) 72mm x (H) 81mm x (D) 68mm. It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure. The operating temperature is from -5°C to 40°C. The storage temperature is from -30°C to 70°C.